Start via ADCL WinSoft¶
ADCL WinSoft is the long-term replacement for AeroWare. It runs the VFD and the DAQ from one application. This page is the per-run startup sequence; the application's internals are in Software → ADCL WinSoft.
Prerequisites¶
- Pre-run checklist complete.
- Main switch closed (mains live to the VFD), drive keypad shows
REM. - Lab PC powered, Ethernet 4 holding
192.168.50.100.
Launch¶
Double-click E:\Wind_tunnel\ADCLWinSoft\ADCL WinSoft.exe. The application takes a few seconds to start (the PyInstaller bundle is ~65 MB and unpacks to a temporary folder).
On first launch only the application asks for:
- an admin password (used to access the calibration / channel-map / password-change tabs); minimum 6 characters. The hash is written to
%APPDATA%\AeroLab\ADCLWinSoft\admin.hash. - a model characteristic length (used for the live Reynolds-number display in the side panel).
Subsequent launches go straight to the main window.
Connect to the drive¶
- Open the VFD tab.
- Verify the Modbus connection indicator in the footer goes green. If it does not, see Troubleshooting → Modbus connection.
- The status panel should show the drive's quick-access registers updating at 4 Hz: CW, REF1, SW, ACT1 (speed), ACT2 (current).
Start the DAQ (optional but recommended)¶
If you want data recorded:
- Confirm the footer says DAQ: cDAQ1, not "DAQ: simulated".
- In the right-column DAQ Gate, press Start DAQ.
- The Signals tab now shows live engineering-unit readings; the Graphs tab shows the rolling buffers.
Set the speed reference¶
- In the right-column Quick Tunnel panel, drag the slider to your initial RPM setpoint (range 0–880 RPM).
- Press Apply Setpoint. This writes REF1 only — it does not start the motor.
- The drive's keypad shows the new setpoint as a frequency reference.
Start the motor¶
- Visually confirm the test section is clear of people and tools (one more time).
- Press Start Tunnel. ADCL WinSoft writes the start sequence (REF1 → CW=0x0476 → CW=0x047F) with the timing the drive requires.
- The Status panel shows the drive transition to RUN. The Speed RPM readout begins to climb.
- The motor reaches the commanded RPM in a few seconds (per the drive's
ACCEL TIMEparameter).
Change setpoint mid-run¶
Move the Quick Tunnel slider and press Apply Setpoint. ADCL WinSoft writes only REF1, never re-issues the start word; the drive ramps smoothly to the new RPM.
Never press Start Tunnel mid-run
Pressing Start Tunnel again writes 0x0476 followed by 0x047F. Writing 0x0476 first stops the drive. This is a quirk of the ABB Drives profile; ADCL WinSoft's command worker exists in part to make this distinction explicit (SetRpmCmd vs StartCmd). For the user it means: use Apply Setpoint for any mid-run change, and Start Tunnel only from idle.
During the run¶
The right-column Quick Tunnel panel shows the requested vs actual RPM. The VFD tab shows the raw register values. The Signals tab shows the engineering-unit DAQ readings. The Graphs tab shows the rolling buffers (last 4096 samples per channel, FIFO).
Watch the footer for:
- the Connected indicator on the Modbus side;
- the DAQ indicator;
- any fault message from the drive (which appears as a red status banner with the fault code).
If a fault appears, Troubleshooting → Faults and alarms is the first stop.
Stop the motor¶
Two options:
- Stop Tunnel (preferred for normal end of run): ramp-stop per the drive's
DECEL TIME. - Emergency Stop (red, larger button): coast-stop with
CW=0x0000andREF1=0.
Both write the appropriate Modbus registers. The Status panel reflects the transition.
For the rest of the shutdown sequence (smoke, laser, lights, mains), see Shutdown.